Detuned capacitor banks

All electrical devices require active power to operate. Many electrical devices, such as electric motors, also require reactive power to operate. Reactive power can be drawn from the grid, but in that case, the network operator charges a reactive power fee. Another option is to produce reactive power locally using a detuned capacitor bank.

Reactive power requirement

Harmonic currents occur in electrical power systems due to nonlinear loads such as computers, frequency converters, and UPS systems. Harmonic currents cause, for example, increased losses and malfunctions in electrical equipment. The detuned capacitor bank filters out ordinary harmonic currents.

When selecting a detuned capacitor bank, it is essential to know the site’s reactive power requirement and how the requirement varies. The electricity bill usually reveals the reactive power requirement. In more complex installations, the reactive power requirement and harmonic currents can be determined through measurements.

Selecting a detuned capacitor bank

A detuned capacitor bank consists of appropriate compensation stages. The stages are selected based on variations in the site’s compensation requirements. Typically, a suitable combination of small (e.g., 12.5 kvar), medium (e.g., 25 kvar), and large (e.g., 50 kvar) compensation stages is required. The compensation stages are controlled by a regulator that switches them on or off according to the reactive power needed at any given moment. If a conventional floor-standing detuned capacitor bank is too large to fit or if floor installation is not an option, we recommend using a wall-mounted bank.

The detuned capacitor bank is tuned to a frequency that is not found in the network (in Finland, this is typically 189 Hz). Other tuning frequencies can also be used.

Features

– 400 V, 50 Hz
– Tuning frequency: 189 Hz
– Control with 6, 12, 18 or 24 steps, as required
– Cabling direction from above
– Filter fan
– Enclosure rating IP30
– Indoor installation, 0–35°C

Selecting a detuned capacitor bank

– Voltage level other than 400 V, such as 690 V
– Tuning frequency other than 189 Hz –
for example, 134 or 141 Hz.
– Outdoor installation: IP43, -25°C – (+35°C)
– Cable routing from the bottom or the side
– Slave battery without a controller

Reactive power calculator for dimensioning detuned capacitor banks

Enter the active power (kW), the power factor at the outset, and the desired power factor here. The calculator provides you with the required compensation power.

Power factor compensation

0.82
0.95
Required compensation power (Q)
698 kVAr
Styles table
Product Power (kvar) Stages (kvar) Current (A) Dimensions (width x depth x height) Weight (kg) Heat losses (W/kvar) Fuse (A) Cable (Cu/mm², recommended) E number
TKF-E23/3+7.5+12.5/400-50-189 23 3 +7.5 + 12.5 33 800 x 600 x 1150 100 10.5 3 x 50 3 x 16 + 16 5714735
TKF-E35.5/3+7.5+2x12.5/400-50-189 35.5 3 + 7.5 + 2 x 12.5 51 800 x 600 x 1150 115 10 3 x 80 3 x 25 + 16 5714737
TKF-E45/7.5+12.5+25/400-50-189 45 7.5+12.5+25 65 800x600x1150 130 8.1 3x100 3 x 50 + 25 5714700
TKF-E70/7.5+12.5+2x25/400-50-189 70 7.5 + 12.5 + 2 x 25 101 800x600x1150 150 7.7 3x160 3 x 70 + 35 5714704
TKF-E75/2x12.5+2x25/400-50-189 75 2x12.5+2x25 108 800x600x1150 150 7.7 3x160 3 x 70 + 35 5714703
TKF-E95/7.5+12.5+25+50/400-50-189 95 7.5+12.5+25+50 137 800x600x1150 180 7.3 3x200 3 x 120 + 70 5714707
TKF-E100/2x12.5+25+50/400-50-189 100 2 x 12.5 + 25 + 50 144 800x600x1150 180 7.3 3x200 3 x 120 + 70 5714706
TKF-E125/2x12.5+2x25+50/400-50-189 125 2x12.5+2x25+50 180 800x600x1150 190 7.3 3x250 2 x (3 x 70 + 35) 5714766
TKF-E150/2x12.5+25+2x50/400-50-189 150 2x12.5+25+2x50 217 800x600x1150 200 7.1 3x315 2 x (3 x 70 + 35) 5714710
TKF-E175/25+3x50/400-50-189 175 25+3x50 252 800x600x2000 280 6.7 3x315 2 x (3 x 95 + 50) 5714712
TKF-E200/2x12.5+25+3x50/400-50-189 200 2x12.5+25+3x50 288 800x600x2000 320 7 3x400 2 x (3 x 95 + 50) 5714715
TKF-E225/25+4x50/400-50-189 225 25+4x50 324 800x600x2000 350 6.7 3x400 2 x (3 x 120 + 70) 5714716
TKF-E250/2x25+4x50/400-50-189 250 2x25+4x50 361 800x600x2000 380 6.7 3 x 500 2 x (3 x 150 + 70) 5714722
TKF-E300/2x25+5x50/400-50-189 300 2x25+5x50 433 800x600x2000 450 6.7 3 x 630 2 x (3 x 185 + 95) 5714724
TKF-E300/6x50/400-50-189 300 6x50 433 800x600x2000 450 6.6 3 x 630 2 x (3 x 185 + 95) 5714720
TKF-E400/2x50+4x75/400-50-189 400 2x25+50+4x75 577 1200x600x1800 520 6.2 3 x 800 2 x (3 x 240 + 120) 5714767

See our specialised banks

We also manufacture products with other features, such as products for different voltage levels or with non-standard dimensions.

Download the operating manual for the detuned capacitor bank

We conduct power quality measurements on-site and provide recommendations for corrective actions. We manufacture compensation and harmonic filtering products tailored to our clients’ needs at our own production facility. We provide equipment inspections and maintenance.

Download the reactive power guide

The guide provides a step-by-step overview of how to select a
detuned capacitor bank for reactive power compensation. After reading this, you will have a basic understanding of the topic, and you will be able to select the right equipment for your application. The table on the last page provides all the relevant technical information, including information for device installation.

Spare parts for detuned capacitor banks

***TKF spare parts are compatible with most detuned capacitor banks. For example, spare parts for older detuned capacitor banks from Nokia Capacitors, Alstom Grid, or GE Grid Solutions.

Styles table
Spare part TKF spare part TKF E-number Nokian Capacitors component*** Nokian Capacitors E-number***
Capacitor unit TKF-U12.5/400-50 5714728 FL1D 15/400-50 15 kVAR 5705322
Capacitor unit TKF-U25/400-50 5714729 FL2D 50/400-50 50 kVAR 5705326
Capacitor unit TKF-U50/400-50 5714730 FL2D 50/400-50 50 kVAR 5705328
Reactive power controller TKF-CXplus12 5714733 NC-12 5705493
Filter fabric NC D filter FILTER MAT AM25P 5705794
Other Whether you need a contactor, a detuned capacitor, a filter fan, or a thermostat, you can contact us!

TKF's solutions are used at thousands of sites, ranging from office buildings to industrial facilities

Needs range from standard reactive power compensation to demanding applications that are critical to society. Hospitals (such as Tampere University Hospital and Satakunta Central Hospital in Finland), the Finnish Defence Forces, infrastructure projects (Helsinki Airport and the Helsinki metro), industry, real estate companies (VVO, Senate Properties), and electrical installations.